For the complete documentation index, see llms.txt. This page is also available as Markdown.

overview

The Clean Air Tower Einweg (disposable filter) is KEMPER's air filtration tower with replaceable filter cartridges. It provides advanced monitoring of motor performance and operating conditions.

Device Identification

Property
Value

Slug

clean-air-tower-einweg

Type

Air Filtration Tower

Filter Type

Disposable

Purpose

The Clean Air Tower (Disposable Filter) is designed to:

  • Filter welding fumes and particulates

  • Use replaceable filter cartridges

  • Provide detailed motor monitoring

  • Support industrial air quality improvement

Key Measurements

Motor Status

Measurement
Field
Unit
Description

Motor Running

MOTOR_RUNNING

Boolean

Motor operating state

Motor Power

MOTOR_ACTUAL_POWER

kW

Current power consumption

Motor Frequency

MOTOR_FREQUENCY

Hz

Operating frequency

Motor Current

MOTOR_CURRENT

A

Current draw in Amps

Motor Temperature

TEMPERATURE_MOTOR

°C

Motor temperature

Boost Mode

BOOST_MODE_ACTIVE

Boolean

Boost mode status

Air Flow

Measurement
Field
Unit
Description

Volume Flow

ACTUAL_VOLUMEFLOW

m³/h

Air volume being filtered

Service

Measurement
Field
Unit
Description

Operating Hours

OPERATING_HOURS

h

Total motor running time

Hours Until Service

MAINTENANCE_HOURS

h

Time until maintenance

System

Measurement
Field
Description

Fault Code

FAULT_CODE

Current fault (0 = OK)

Signal Strength

RSSI

Cellular signal quality

Status Indicators

Status
Description

Running

Motor actively operating

Stopped

Motor not running

Normal Mode

Standard operation

BOOST

Boost mode active

Error

Fault code detected

Boost Mode

  • Indicated by "BOOST" badge

  • Increases motor power

  • Higher air volume flow

  • Used for demanding conditions

Fault Codes

Fault code list (click to expand)
Code
Description

0

No fault (OK)

E02

Airflow control error

E03

Maintenance required

E04

Motor temperature too high

E07

Modbus error

E12

Airflow too low

Device Tabs

Tab
Description
Documentation

Dashboard

Motor status and measurements

Dashboard

History

Performance history

History

Functions

Start/Stop control

Functions

License

License management

Settings

Fault codes and info

Settings

Automation Target

Can be controlled by automation rules:

  • Triggered by AirWatch PM10 levels

  • Automatic start on high pollution

  • Automatic stop when air quality improves

See Automation Rules.

Scheduler Support

Supports time-based scheduling:

  • Define operating hours

  • Configure days of week

  • Automatic on/off control

See Schedulers.

Differences from Self-Cleaning Model

Feature
Einweg (Disposable)
Abreinigbar (Self-Cleaning)

Filter Type

Replaceable cartridges

Self-cleaning

Compressed Air

Not required

Required

Cleaning Cycles

N/A

Automatic

Motor Monitoring

Advanced

Basic

Boost Mode

Yes

No

Title

Dashboard — Current measurements

Target
Title

Functions — Device control

Target